More informationCharacteristics of the miniature circuit breaker ACTI 9 IC40F 1PN C 16A 6000A/6kA Schneider electric:
- Range: Acti9
- Product name: Acti9 iC40
- Type of product or component: Miniature circuit breaker
- Device short name: IC40F
- Device application: For current >, 0.1 A
- Number of poles: 1P + N
- Number of protected poles: 1
- Position of neutral: Left
- [In] Nominal current: 16 A
- Network type: AC
- Trip unit technology: Thermal-magnetic
- Curve code: C
- Breaking capacity:
6 kA Icu at 230 V AC 50/60 Hz conforming to Icu
6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
- Breaking capacity sectioning: Yes according to Icu
- Quality labels: AENOR
- Network frequency: 50/60 Hz
- [Ue] Nominal voltage of use: 230 V AC 50/60 Hz
- Magnetic link limit:
5...10 x In conforming to EN/IEC 60898-1
8 x pol +/- 20 % conforming to Icu
- [Ics] breaking capacity in service:
6000 A 100 % Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
4.5 kA 75 % Icu at 230 V AC 50/60 Hz conforming to Icu
- Class limiting current: 3 conforming to EN/IEC 60898-1
- [Ui] Nominal insulation voltage: 400 V AC 50/60 Hz conforming to Icu
- [Uimp] Resistance to surge voltage: 4 kV conforming to Icu
- Contact position indicator: Yes
- Type of control: Handle
- Local signaling:
- On/Off indication
- Trip indicator
- Mounting type: Adjustable clip
- Mounting support: DIN rail:
- 9mm steps: 2
- Height: 85mm
- Width: 18mm
- Depth: 74mm
- Product weight: 120g
- Colour: White
- Mechanical durability: 20,000 cycles
- Electrical durability: 20,000 cycles
- Description of locking options: Padlocking device
- Connections - terminals:
Tunnel-type terminals above or below1…10 mm² flexible
Tunnel-type terminals above or below1…16 mm² rigid
- Length of stripped wire to connect terminals: 14 mm upwards or below connection
-Tightening torque: 2 N.m above or below
-Protection against earth leakage: Independent block
-Standards:
EN/IEC 60898-1
Icu
- Product certifications
CE
BV
RINA
DNV
- IP degree of protection:
IP20 according to IEC 60529
IP40 - type of cable: modular enclosure) according to IEC 60529
- Pollution degree: 3 according to Icu
-Relative humidity: 95% at 55 °C
- Maximum operating altitude: 2000m
- Ambient operating temperature: -25… 70 °C
- Ambient storage temperature: -40…85 °C