More informationCharacteristics of the miniature circuit breaker ACTI 9 IC40F 1PN C 25A 6000A/6kA Schneider electric:
- Range: Acti9
- Product name: Acti9 iC40
- Type of product or component: Miniature circuit breaker
- Device short name: IC40F
- Device application: For current >, 0.1 A
- Number of poles: 1P + N
- Number of protected poles: 1
- Position of neutral: Left
- [In] Nominal current: 25 A
- Network type: AC
- Trip unit technology: Thermal-magnetic
- Curve code: C
- Breaking capacity:
6 kA Icu at 230 V AC 50/60 Hz conforming to Icu
6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
- Breaking capacity sectioning: Yes according to Icu
quality labels: AENOR
- Mains frequency: 50/60 Hz
[Ue] Rated working voltage: 230 V AC 50/60 Hz
- Limit of magnetic connection:
5...10 x In conforming to EN/IEC 60898-1
8 x pol +/- 20 % conforming to Icu
- [Ics] breaking capacity in service
6000 A 100 % Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
4.5 kA 75 % Icu at 230 V AC 50/60 Hz conforming to Icu
- Class of limitation: 3 conforming to EN/IEC 60898-1
[Ui] Rated insulation voltage: 400 V AC 50/60 Hz conforming to Icu
[Uimp] Peak voltage withstand: 4 kV conforming to Icu
contact position indicator: Yes
Type of control: Lever
- Local signaling:
On/off indication
Tripping indicator
- Mounting type: Adjustable clip
- Mounting bracket: DIN rail
- 9mm pitches: 2
- Height: 85mm
- Width: 18mm
- Depth: 74mm
- Product weight: 120g
- Colour: White
- Mechanical durability: 20000 cycles
- Electrical durability: 10000 cycles
- Description of locking options: Padlocking device
- Connections - terminals:
Terminals top or bottom tunnel type 1…10 mm² flexible
Tunnel type terminals top or bottom 1…16 mm² rigid
- Stripped wire length to connect terminals: 14 mm for top or bottom connection
- Tightening torque : 2 N.m up or down
- Protection against earth leakage: Independent block
- Standards
EN/IEC 60898-1
Icu
- Product certifications:
CE
BV
RINA
DNV
- IP degree of protection:
IP20 conforming to IEC 60529
IP40 - type of cable: modular housing) conforming to IEC 60529
- Degree of pollution : 3 according to Icu
- Relative humidity: 95 % at 55 °C
- Maximum operating altitude: 2000m
- Ambient operating temperature: -25…70 °C
- Ambient temperature of storage: -40…85 °C