More informationCharacteristics of the circuit breaker - 2P - 25A - Curve C - 6kA Schneider electric:
- Application of the device: For current>, 0.1 A
- Range: Acti 9
- Name of the product: Acti 9 iKQ
- Product or component type: Miniature circuit breaker
- Device short name: IK60N
- Number of poles: 2P
- Number of protected poles: 2
- [In] Nominal current: 25 A at 30 °C
- Network type: AC
- Trip unit technology: Thermal-magnetic
- Curve code: C
- Breaking capacity: 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
- Isolating capacity: Yes conforming to EN/IEC 60898-1
- Standards: EN/IEC 60898-1
- Product certifications: Aenor
- Mains frequency: 50/60 Hz
- Magnetic link limit: 5...10 x In
- [Ics] breaking capacity in service: 6000 A 100% conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
- Class of limitation: 3 conforming to EN/IEC 60898-1
- [Ui] Rated insulation voltage: 440 V AC 50/ 60 Hz conforming to EN/IEC 60898-1
- [Uimp] Resistance to voltage spikes: 4 kV conforming to EN/IEC 60898-1
- Type of control: Handle
- Local signaling: On/Off indication
- Mounting type: Adjustable clip
- Mounting support: DIN rail
- 9mm steps: 4
- Height: 85mm
- Width: 36mm< br>- Depth: 78.5mm
- Product weight: 200g
- Colour: White
- Mechanical durability: 20,000 cycles
- Electrical durability: 10,000 cycles
- Description of options locking: Padlocking device
- Connections - terminals:
Tunnel type terminal - cable type: top or bottom) 1…25 mm² rigid
Tunnel type terminal - cable type: top or bottom ) 1…16 mm² flexible
- Length of bare wire to connect terminals: 14 mm for top or bottom connection
- Tightening torque: 2 N.m top or bottom
- Protection against earth leakage: Without< br>- IP degree of protection: IP20 conforming to IEC 60529
- Pollution degree: 2 conforming to EN/IEC 60898-1
- Overvoltage category: III
- Ambient operating temperature: -25 …60 °C
- Ambient storage temperature: -40…85 °C