More informationCharacteristics of the 4P, 40A, 300mA type AC differential switch:
- Neutral position: Right
- Number of poles: 4 P
- Mounting: DIN rail
- Number of modules: 4
- Rated AC operating voltage: 230 / 400 V
- Rated frequency: 50 Hz
- Rated insulation voltage: 500 V
- Rated impulse withstand voltage: 4000 V
- Current Rated differential current: 300 mA
- Rated rated current: 40 A
- Resistance to current wave 8/20µs: 0.25 kA
- Closing and breaking power: 1.5 kA
- Conditional current Rated short-circuit current Inc according to EN 61008-1: 6 kA
- Depth of installed product: 70 mm
- Height of installed product: 83 mm
- Width of installed product: 70 mm
- Dimensions construction (DIN 43880): 1
- Frequency: 50 Hz
- Total power dissipated under conditions of Nominal intensity: 8.1 W
- Power dissipated per pole: 3.6 W
- Protected against untimely trips : No
- Quick trip (Short time): No
- Electrical endurance in number of cycles: 2000
- Mechanical endurance in number of maneuvers: 4000
- Superior connection type for modular devices: Terminal with screws
- Tightening torque: 2.8 Nm
- Type of top clip for modular devices: Not applicable
- Type of DIN profile fixing clip for modular devices: Metallic
- Type of lower connection for modular devices: Double connection terminal
- Upper detachability for modular devices: No
- Lower detachability for modular devices: No
- Rigid cable connection section in screw terminals on the back upper: 1 / 25 mm²
- Flexible cable connection section: 16 mm²
- Upper terminal connection section. in rigid cable: 1 / 25 mm²
- Connection section of screw terminals in stud with flexible cable: 1 / 16 mm²
- Connection section of stud terminals with screw: 1 / 16 mm²
- IP protection index: IP20
- Differential protection type: AC
- Operating temperature: -25…40 °C
- Altitude: 2000 m
* All information in The datasheet