More informationThese contactors are made for use in domestic applications as well as in industrial settings.
They are provided with the following benefits, hum-free operation, low power consumption, and built-in surge protection.
20A installation contactor features:
- Nominal operating voltage:
Main circuit 220 V DC
Main circuit 250 V AC
- Nominal voltage of the control circuit (U c): 230 V
- Nominal frequency (f):
Control circuit DC control circuit
50 Hz
Control circuit 60 Hz
Control circuit 400 Hz
Circuit
main DC Main circuit 50 Hz
Main circuit 60 Hz
- Nominal operating current AC-1 (I e): (NO) 20 A
- Nominal operating current AC-3 (I e): (230 V) Single phase, NO 9 A
- Rated operating power AC-1 (P e): (230 V) Single phase, NO 4.6 kW
- Nominal operating power AC-3 (P e): (230 V) Single phase, NO 1.3 kW
- Nominal operating current AC-7a (I e): (NO) 20 A
- Nominal operating power AC-7a (P e): (230 V) Single phase, NO 4.6 kW
- Nominal operating current AC-7b (I e): (230 V) Single phase, NO 9 A
- Nominal operating power AC-7b (P e): (230 V) Single phase, NO 1.3 kW
- Recommended screwdriver:
Pozidriv 1 control circuit
Pozidriv 1 Main Circuit
- Nominal impulse withstand voltage (U imp): 6 kV
- Nominal insulation voltage (U i): 400 V
- Main circuit of connection capacity:
Flexible with sleeve 1x 1 ... 6 mm²
Flexible with sleeve 2x 1 ... 2.5 mm²
Flexible with insulated sleeve 1x 1 ... 6 mm²
Flexible with insulated bushing 2x 1 ... 1.5 mm²
Flexible 1x 1 ... 6 mm²
Flexible 2x 1 ... 4 mm²
Rigid 1x 1 ... 10 mm²
Rigid 2x 1 ... 4 mm²
- Connection of the capacity control circuit:
Flexible with sleeve 1x 1 ... 2.5 mm²
Flexible with sleeve 2x 0.75 ... 1.5 mm²
Flexible with insulated sleeve 1x 1 ... 2.5 mm²
Flexible with insulated ferrule 2x 0.75 ... 1 mm²
Flexible 1x 1 ... 2.5 mm²
Flexible 2x 1 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.75 ... 2.5 mm²
- Torque:
Control circuit 0.9 Nm
Main circuit 1.2 Nm
- Cable stripping length:
Control circuit 7 mm
Main circuit 10 mm
- Degree of protection: IP20
- Electrical durability:
AC-1 (NO) 150000 cycle
AC-3 (NO) 150000 cycle
AC-7a (NO) 150000 cycle
AC-7b (NO) 150000 cycle
- Mechanical durability: 1000000 cycle
- Number of poles: 2
- Number of main NC contacts: 0
- Number of main NO contacts: 2
- Width in number of modular spaces: 1
- Pollution degree: 3
- Standards:
IEC / EN 60947-1
IEC / EN 60947-4-1
UL 60947-1
UL 60947-4-1
IEC / EN 61095